Selecting a generator — what to account for

Most generator regrets come from one of two mistakes: buying too small (unit overloads and trips out), or buying the wrong type (petrol when diesel was needed, single-phase when three-phase was needed). The framework below avoids both — work through every question before asking for a quote.

01

Question 1 — What's the running load?

List every appliance, motor, light, and pump that will run simultaneously. Add up the running watts (NOT the surge / peak watts) — that's your continuous load. For a typical 4-bedroom home with fridge + lighting + TV + fans + internet + medical equipment, you're looking at 4–6 kW continuous.
02

Question 2 — What surge currents are present?

Motors (air-con, well pumps, fridges, deep freezes) draw 4–7× their running watts for the first 200 ms when starting. Air-conditioners are usually the killer load. Either add up the biggest motor's surge wattage, or use the LRA (Locked-Rotor Amps) from the appliance nameplate × voltage to get surge kVA. The generator's kVA rating must exceed this.
03

Question 3 — Diesel or petrol?

If it's backup or prime-power (>500 hrs/year), diesel. If it's camp/portable < 4 kVA, petrol inverter. (See Article 03.)
04

Question 4 — Single-phase or three-phase?

Check your existing main switchboard. If it has only red, white, blue, and neutral cables coming in (three live wires), you have three-phase power and need a three-phase generator. If only one live + neutral, you're single-phase. Most homes are single-phase; most workshops and commercial buildings are three-phase.
05

Question 5 — Where will it live?

Outdoor canopied (most common), indoor plant room, on a trailer? Each has different noise and ventilation requirements. A bare open-frame unit at 7 m can hit 95 dB(A); a sound-attenuated canopy unit at 7 m runs at 65 dB(A) — a 30 dB difference, perceived as about 8× quieter.
06

Question 6 — Future-proofing

Generators last 15–25 years. Will you be adding solar, a heat pump, or an EV charger in that time? Add 20–25% headroom over today's load to absorb future expansion without needing to replace the genset.
Quick answers

FAQs

Don't see your question? Call 07 5529 0351 or contact us.

Yes, with an Automatic Transfer Switch (ATS) wired into your main board. The generator picks up the entire house on mains failure and drops it on mains return.

Need to talk to a real generator engineer?

We answer the phone and we answer the questions. No call centres, no sales scripts.