- Model
- GDW550V/FS2
- Available configurations
- GDW550V+MFT-M - SF501TWAD2C (2300 L)
- Standby / LTP output
- 556.9 kVA / 445.5 kW
- Prime / PRP output
- 506 kVA / 404.8 kW
- Voltage
- 400/230 V
- Phase
- Three-phase
- Frequency
- 50 Hz
- Power factor
- 0.8
- Generator maximum output current
- 804 A
- Generator nominal output current
- 730 A
- Generator circuit-breaker rating
- 800 A
- Engine starting battery voltage
- 24 V DC
- Engine
- Volvo TAD1346GE
- Engine speed
- 1500 rpm
- Engine cooling
- Water
- Engine cylinders/displacement
- 6 in line; 12780 cm³
- Aspiration
- Turbocharged
- Governor
- Electronic
- Gross engine power
- 482 kWm ESP; 439 kWm PRP
- Emissions level
- Stage II
- Fuel
- Diesel
- Fuel tank size
- MFT-M 2300 L
- Runtime @ 75% load
- MFT-M (2300 L) 29.43 h
- Fuel consumption @100% load
- 99.82 L/hr
- Dimensions/weight
- Canopy: 4500 x 1590 x 2762 mm, 5619 kg; Extra silent (Custom Order): 6100 x 1590 x 2762 mm, 6036 kg
- Noise @ 7m
- 75 dB(A) canopy @ 7 m; 72 dB(A) Extra silent (Custom Order) @ 7 m
- Canopy
- Sound-attenuated, traffic white RAL9016
- Alternator
- Mecc Alte ECO40 1L4 C
- Alternator rating
- 601 kVA standby @ 27°C; 550 kVA continuous @ 40°C
- Alternator efficiency
- 94.8% @ 100% load
- Alternator voltage tolerance
- 0.5%
- IP protection
- IP23
- Cooling/airflow
- 469 m³/min
- Item number
- SF501TWAD2C
- Fuel consumption @ 75% load
- 78.16 L/hr