- Model
- GDW335V/FS2
- Available configurations
- GDW335V+MFT-M - BT311TWA005 (1000 L)
- Standby / LTP output
- 330 kVA / 264 kW
- Prime / PRP output
- 300 kVA / 240 kW
- Voltage
- 400/230 V
- Phase
- Three-phase
- Frequency
- 50 Hz
- Power factor
- 0.8
- Generator maximum output current
- 476 A
- Generator nominal output current
- 433 A
- Generator circuit-breaker rating
- 630 A
- Engine starting battery voltage
- 24 V DC
- Engine
- Volvo TAD1342GE
- Engine speed
- 1500 rpm
- Engine cooling
- Water
- Engine cylinders/displacement
- 6 in line; 12780 cm³
- Aspiration
- Turbocharged
- Governor
- Electronic
- Gross engine power
- 343 kWm ESP; 313 kWm PRP
- Emissions level
- Stage II
- Fuel
- Diesel
- Fuel tank size
- MFT-M 1000 L
- Runtime @ 75% load
- MFT-M (1000 L) 21.6 h
- Fuel consumption @100% load
- 60.83 L/hr
- Dimensions/weight
- Canopy: 4000 x 1460 x 2147 mm, 3891 kg; Extra silent (Custom Order): 5286 x 1460 x 2147 mm, 4222 kg
- Noise @ 7m
- 68 dB(A) canopy @ 7 m; 64 dB(A) Extra silent (Custom Order) @ 7 m
- Canopy
- Sound-attenuated, traffic white RAL9016
- Alternator
- Mecc Alte ECO38 1L4 C
- Alternator rating
- 330 kVA standby @ 27°C; 300 kVA continuous @ 40°C
- Alternator efficiency
- 93.7% @ 100% load
- Alternator voltage tolerance
- 1%
- IP protection
- IP23
- Cooling/airflow
- 458 m³/min
- Item number
- BT311TWA005
- Fuel consumption @ 75% load
- 46.29 L/hr