- Model
- GDW280V/FS2
- Available configurations
- GDW280V+MFT-M - BT251TWA006 (1000 L)
- Standby / LTP output
- 275 kVA / 220 kW
- Prime / PRP output
- 250 kVA / 200 kW
- Voltage
- 400/230 V
- Phase
- Three-phase
- Frequency
- 50 Hz
- Power factor
- 0.8
- Generator maximum output current
- 397 A
- Generator nominal output current
- 361 A
- Generator circuit-breaker rating
- 400 A
- Engine starting battery voltage
- 24 V DC
- Engine
- Volvo TAD841GE
- Engine speed
- 1500 rpm
- Engine cooling
- Water
- Engine cylinders/displacement
- 6 in line; 7700 cm³
- Aspiration
- Turbocharged
- Gross engine power
- 254 kWm ESP; 232 kWm PRP
- Fuel
- Diesel
- Fuel tank size
- MFT-M 1000 L
- Runtime @ 75% load
- MFT-M (1000 L) 23.93 h
- Fuel consumption @100% load
- 53.3 L/hr
- Dimensions/weight
- Canopy: 3702 x 1200 x 2390 mm, 3111 kg; Extra silent (Custom Order): 3950 x 1200 x 2860 mm, 3833 kg
- Noise @ 7m
- 68 dB(A) canopy @ 7 m; 64 dB(A) Extra silent (Custom Order) @ 7 m
- Canopy
- Sound-attenuated, traffic white RAL9016
- Alternator
- Mecc Alte ECO38 2M4 C
- Alternator rating
- 275 kVA standby @ 27°C; 250 kVA continuous @ 40°C
- Alternator efficiency
- 93.4% @ 100% load
- Alternator voltage tolerance
- 1%
- IP protection
- IP23
- Cooling/airflow
- 342 m³/min
- Item number
- BT251TWA006
- Data Centre Power / DCP output
- 250 kVA / 200 kW
- Fuel consumption @ 75% load
- 41.79 L/hr