GDW110P
Protect operations from costly outages with the Pramac GDW110P. Rated at 100 kVA prime and 110 kVA standby, it is designed for commercial standby, industrial backup and site power. The set can be matched to the real load, motor-starting demands and operating environment rather than selected on nameplate size alone. The Perkins 1104C-44TAG2 engine and Mecc Alte ECP34-2S 4C alternator form a well-matched mechanical and electrical package for long-term standby or prime-power service. Integrate it with automatic transfer switching, remote monitoring, distribution and site fuel systems to create a complete power solution. Order the standard package or specify a custom build with a stainless-steel canopy, hot-dip galvanised skid base, super-silent enclosure, synchronising controls or an open generator set. Talk to Capital Power Systems about generator sizing, transfer switching, fuel autonomy, acoustic treatment and a complete turnkey installation.
Download Specification Sheet→- 400/230 V, 50 Hz, three-phase output at 0.8 power factor
- 110 kVA / 88 kW ESP and 100 kVA / 80 kW PRP rating
- Perkins 1104C-44TAG2 1500 rpm water-cooled diesel engine
- Mecc Alte ECP34-2S 4C alternator, IP23, Class H insulation
- 75% PRP fuel consumption: 17.37 L/hr
- Fuel tank/runtime options: 8PFT (350 L) 20.15 h; | MFT-S (350 L) 20.15 h; | MFT-M (500 L) 28.79 h; | MFT-L (1000 L) 57.57 h
- Noise pressure: 66 dB(A) canopy @ 7 m; | 64 dB(A) Extra silent (Custom Order) @ 7 m
Industry-leading components, fully supported in Australia

Pramac
Pramac is a leading global manufacturer of stationary and mobile power generation equipment, founded in Casole d'Elsa, Tuscany in 1966. Now part of the Generac group, Pramac engineers diesel, petrol and battery energy storage solutions trusted by rental houses, mining sites and emergency services in over 150 countries.
Deep Sea Electronics
Deep Sea Electronics (DSE) has been designing intelligent generator and battery management controllers from Hunmanby, UK since 1975. Their controllers — including the iconic DSE 4520, 6020 and 7320 series — set the global standard for AMF / ATS automation, remote monitoring and over-current protection.
Perkins — Engine
Perkins is a British diesel engine manufacturer (part of Caterpillar Inc. since 1998), with engines in production since 1932 and over 22 million units built. Perkins powers the bulk of industrial-class Pramac generators — the 1100, 1300, 1700, 2200, 2500, and 4000 Series engines have a global service network and a reputation for reliability under continuous and prime-power duty cycles.
Mecc Alte — Alternator
Mecc Alte is the world's largest independent alternator manufacturer, headquartered in Vicenza, Italy since 1947. Their brushless synchronous alternators are renowned for exceptional voltage regulation, high efficiency and long service life — the engineering backbone of countless premium gensets.
- Model
- GDW110P+PFT
- Prime Power RPR
- TBC — refer to datasheet
- Emergency Stand-By Power ESP
- TBC — refer to datasheet
- Continuous power
- 88.0 kW
- Voltage
- 400/230 V
- Phase
- Three-phase
- Frequency
- 50 Hz
- Power factor
- 0.8
- Fuel
- Diesel
- Fuel Tank Size
- 350 L
- Run time @ 75% Load
- 15.85 hrs
- Engine
- Perkins 1104C-44TAG2
- Emission Level
- TBC — refer to datasheet
- Alternator
- Mecc Alte ECP34-2S 4C
- Noise @ 7 m
- 66 dB(A) canopy @ 7 m; | 64 dB(A) Extra silent (Custom Order) @ 7 m
- Product type
- stationary diesel generator set
- Standby / ESP output
- 110 kVA / 88 kW
- Prime / PRP output
- 100 kVA / 80 kW
- Engine speed
- 1500 rpm
- Engine cooling
- Water
- Engine cylinders/displacement
- 4 in line; | 4400 cm³
- Aspiration
- Turbocharged
- Governor
- Electronic
- Gross engine power
- 103 kWm ESP; | 93.6 kWm PRP
- Alternator rating
- 110 kVA standby @ 27°C; | 100 kVA continuous @ 40°C
- Alternator efficiency
- 92% @ 100% load
- Alternator voltage tolerance
- 1%
- IP protection
- IP23
- Cooling/airflow
- 201 m³/min
- Exhaust gas flow/temp PRP
- 15.2 m³/min; | 543 °C
- Fuel consumption @75% PRP
- 17.37 L/hr
- Fuel consumption @100% PRP
- 21.84 L/hr
- Fuel tank options
- PFT 350 L; | MFT-L 1000 L
- Runtime @75% PRP
- 8PFT (350 L) 20.15 h; | MFT-S (350 L) 20.15 h; | MFT-M (500 L) 28.79 h; | MFT-L (1000 L) 57.57 h
- Electrical
- 12 V battery; | max current 159 A; | nominal current 144 A; | circuit breaker 160 A
- Emissions level
- Stage II
- Application
- commercial standby, industrial backup and site power
- Dimensions/weight
- Canopy: 2757 x 1120 x 1846 mm, 1449 kg; | Extra silent (Custom Order): 2757 x 1120 x 2438 mm, 1619 kg
- Available configurations
- GDW110P+PFT - BT900TPA008 (350 L); | GDW110P-MFT-L - BT900TPA007 (1000 L)
- Item number
- BT900TPA008
Learn more — Generator School
All guides →
Almost every conversation about generator sizing starts with two numbers: kVA and kW. They sound similar, they're closely related, and they're almost always mis-used. The beer-glass analogy below is the fastest way to get them straight in your head — and once you do, every spec sheet in the catalogue suddenly makes sense.

A generator is really three machines bolted together: an engine, an alternator, and a controller. They each do one job, and they all have to talk to each other for the unit to behave properly.

Almost every customer who asks us 'should I get diesel or petrol?' gets the same answer: it depends on the duty. For occasional camp / weekend use under 8 kVA, petrol is cheaper to buy and lighter to move. For anything that has to start reliably after sitting unused — backup, standby, prime-power — diesel wins, almost always.